YB-12/0.4 Outdoor Box-type Substation
General introduction of YB-12/0.4 Outdoor Box-type Substation
Item:YB-12/0.4 Outdoor Box-type Substation
①Easy and flexible installation
②Small and compact
③Safe and reliable operation
④Easy maintenance
⑤Movability
- Introduction
- Contact Now
YBW-35KV Outdoor box-type substation is a complete set of products that assemble voltage switchgear, transformer and low-voltage power distribution equipment into one body. As a power transformation and distribution equipment for urban buildings, living quarters, small and medium-sized factories, mining and oil fields, etc., it has strong complete sets, small size and compact structure, high reliability, small on-site installation workload, short installation height cycle, and Portable and other features. Appropriately change its appearance and color to adapt to the environment, and can also play a role in beautifying the environment.
A set of equipment.
Our YBW-35KV Outdoor box-type substation consists of high voltage switch room, low voltage switch room, relay protection room and transformer room. The shell of high-voltage switch, low-voltage switch room and relay protection room can be made of aluminum alloy plate, steel plate or composite
board making. The surface of the aluminum alloy plate is anodized to enhance the corrosion resistance of the aluminum alloy plate. The steel plate and steel structure parts are all treated by phosphating, and the composite plate has the characteristics of bright color and beautiful appearance, heat insulation and flame retardant. The transformer room does not have a closed shell structure but a high safety net cover, which is not only conducive to the ventilation and heat dissipation of the transformer, but also ensures the safety of people and equipment.
High-voltage switch room HV high-voltage switch room can be equipped with JYNI-35. KYNI0-35 switch cabinet or 35KV load switch. 35KV incoming and outgoing cables can be freely selected by users for overhead cable mode. Low-voltage switch room LV: When the low-voltage side is 10KV, the low-voltage switch room can install X(GN2-1. KZNI-12. KYNI-12 switchgear, HXGNII-10F. HX(GN26-10(F) ring network cabinet. When the low side is 0.4KV, install DWI5T series, ME series, M series, F series frame type circuit breaker and D220 series, CM series, H series, S series in the low voltage switch room (generally do not make low voltage switch cabinet to save space) Series molded case air circuit breakers.
Model Description
YB:Substation
W:Outdoor
▢:Design Number
▢:Transformer capacity (kVA)
35:High voltage side rated voltage (kV)
▢:Low voltage side rated voltage (kV)
Working Environment:
◆The altitude does not exceed 1000m;
◆Ambient temperature: -35C +40C;
◆Relative humidity: the daily average is not more than 95%, and the monthly average is not more than 90%;
◆Installation site: no fire, explosion hazard, chemical corrosive gas and well-ventilated place, The angle of inclination is not more than 30.
Note: When the above normal use conditions are exceeded, the user can negotiate with the company.
Main Technical Parameters
Parameter | Unit | Value | |||
Yuan | Rated frequency | Hz | 50 | ||
Rated voltage | kV | 6 | 10 | 35 | |
Maximum working voltage | kV | 6.9 | 11.5 | 40.5 | |
Rated current | A | 400, 630, 1250 | |||
divert current | A | 1200-3150 | |||
Power frequency withstand voltage to ground and phase-to-phase/isolation ☐ | kV | 42/48 | |||
Lightning impulse withstand voltage ground and phase isolation ☐ | kV | 75/85 | |||
Rated short-circuit breaking current (current limiting fuse) | kA | 31.5 | |||
Variable element | Rated voltage | kV | 6, 10, 35 | ||
Rated Capacity | kVA | 30-2000 | |||
Tap range | % | ±2x2.5%, ±5% | |||
link group | YynO, Dyn11 | ||||
Impedance voltage | % | 4, 4.5, 6, 8 | |||
Low unit | Rated voltage | V | 220, 380, 690, 800 | ||
Main circuit rated current | A | 50-4000 | |||
branch current | A | 5-800 | |||
Shell | Protection class (conventional product) | High voltage room IP33; transformer room IP23; low voltage room IP33 | |||
Noise level | dB | ≤50 |
Structure and Mounting Dimensions
Different appearance
Product Real Shot
Thank you for your attention on Vouchivan ELECTRIC!
We offer Oil immersed transformers, Dry type transformers, Compact transformer substations, etc.Vouchivan Updated
-
Sep 20,2024
How should I choose between an oil-immersed transformer and a dry-type transformer? -
Sep 20,2024
What are the common outdoor substation technologies? -
Sep 20,2024
Causes and Considerations for Oil Leakage and Operating Temperature in Oil-Immersed Transformers