YBD-12/0.4 Outdoor Box-type Substation
General introduction of YBD-12/0.4 Outdoor Box-type Substation
Item:YBD-12/0.4 Outdoor Box-type Substation
①Easy and flexible installation
②Small and compact
③Safe and reliable operation
④Easy maintenance
⑤Movability
- Introduction
- Contact Now
YBD-12/0.4 Outdoor box-type substation is a high-voltage switchgear, distribution transformer and low-voltage power distribution device, which are prefabricated indoor and outdoor compact power distribution equipment in a factory according to a certain wiring scheme. At the same time, it is installed in a moisture-proof, rust-proof, dust-proof, rodent-proof, fire-proof, anti-theft, heat-insulating, fully-enclosed, movable steel structure box, especially suitable for urban network construction and reconstruction. A brand new substation. Box-type substations are suitable for mines, factories, oil and gas fields and wind power stations.
The basic structure of YBD-12/0.4 Outdoor box-type substationis divided into "me" shape and "pin" shape. The frame of the box body is welded with high-quality channel steel and angle steel, which has high mechanical strength. The box body is made of aluminum alloy profiles, which has good anti-corrosion properties. The overall beautiful appearance can be coordinated with the surrounding environment after painting and coloring, and the well-designed bottom lifting device provides great convenience for installation, transportation and movement.
There are independent high-voltage room, transformer room and low-voltage room in the box transformer. The lighting of each room is automatically turned on with the opening of the door. The high-voltage room is equipped with high-ring network switchgear, which can be selected according to the user's needs. Compressor type, vacuum type load switch, and has the "five-proof" function. When the current-limiting high-voltage fuse is used, a certain phase fuse is blown. Automatic opening of the load when the load is closed, avoiding the failure caused by the lack of phase operation
The transformer room adopts natural ventilation and automatic control forced cooling air cooling device. It has an exhaust system that is automatically controlled with temperature changes. It can effectively control and reduce the temperature in the box. It can meet the operating requirements. Device. According to the user's requirements, it can be easily entered and exited from the gate from both sides of the transformer room along the track. The box material can prevent rainwater and dirt from entering. It has the conditions for long-term outdoor use, ensuring anti-corrosion, waterproof, dust-proof performance, long service life, simple maintenance and beautiful appearance.
The transformer can be dry-type or oil-immersed, and the oil-immersed transformer can be fully sealed with oil pillow or without oil pillow.
The low-voltage room has the overall function of low-voltage switchgear, which can be selected by users and combined arbitrarily.
Model Description
YB:Prefabricated Transformer Station
▢:Structural features: P-character shape; M-mesh shape
▢:Design Number
▢:High voltage side rated voltage (kV)
▢:Low voltage side rated voltage (kV)
▢:Transformer rated capacity (kVA)
Working Environment:
◆The altitude does not exceed 1000m;
◆Ambient temperature: -35C +40C;
◆Relative humidity: the daily average is not more than 95%, and the monthly average is not more than 90%;
◆Installation site: no fire, explosion hazard, chemical corrosive gas and well-ventilated place, The angle of inclination is not more than 30.
Note: When the above normal use conditions are exceeded, the user can negotiate with the company.
Main Technical Parameters
Serial number | Name | Unit | High voltage electrical appliances | Transformer | Low voltage electrical appliances |
1 | Rated voltage | kV | 6/10 | 6/0.4 10/0.4 | 0.4 |
2 | Rated Capacity | kVA | 50~ 1600 | ||
3 | Rated current | A | 200, 400, 630 | 100-3200 | |
4 | Rated short-circuit breaking current | A | Load switch 400-630 | 15-63kA | |
kA | Combination switch depends on fuse | ||||
5 | Rated short-time withstand current | kA | 16, 20(4s) | 15(1s) | |
6 | Rated peak withstand current | kA | 31.5, 50 | 30(1s) 30 | |
63 | |||||
7 | Power frequency withstand voltage (1min) | kV | Phase and Phase 32/42 | 25/35 (oil diffuse) | ≤0.3, 2 |
Isolation Fracture 36/48 | 20/28 (dry) | >0.3,2.5 | |||
8 | Lightning impulse withstand voltage (peak) | kV | Phase and Phase 60/75 | 60/75 | |
Isolation Fracture 70/85 | |||||
9 | Cabinet protection level | IP23 | |||
10 | noise level | db | 55 |
Structure and Mounting Dimensions
Different appearance
Product Real Shot
Thank you for your attention on Vouchivan ELECTRIC!
We offer Oil immersed transformers, Dry type transformers, Compact transformer substations, etc.Vouchivan Updated
-
Sep 20,2024
How should I choose between an oil-immersed transformer and a dry-type transformer? -
Sep 20,2024
What are the common outdoor substation technologies? -
Sep 20,2024
Causes and Considerations for Oil Leakage and Operating Temperature in Oil-Immersed Transformers