15 MVA Vacuum Pressure Impregnation VPI Dry Type Transformer
General introduction of 15 MVA Vacuum Pressure Impregnation VPI Dry Type Transformer
The 15 MVA VPI dry type transformer was delivered to Montreal, Canada in 2016, the rated power of the transformer is 15000 KVA.
- Introduction
- Contact Now
The 15 MVA VPI dry type transformer was delivered to Montreal, Canada in 2016, the rated power of the transformer is 15000 KVA. It is a vacuum pressure impregnated winding dry type transformer 24.94kv to 4.16kv, the high voltage of this dry type transformer is 24.94kv, the low voltage is 4.16kv. Variable frequency dephasing dry type transformer have been painted with 3-proofings lacquer and with curing process of high temperature which all can strengthen the anti-short circuit ability. Our 15 MVA dry type transformer was designed with advanced technology and adopts high quality material and components which result in reliable quality and long operation time.
We ensure that each one of our delivered units has undergone rigorous full acceptance testing. We provide one-package service from consulting, quoting, manufacturing, installation, commissioning, training to after sale services, our products are now operating in more than 50 counties in the world. We aim to be your most reliable supplier as well as your best partner in business!
Advantages
Fire resistant /Self-extinguishing(F1)
Environmental class(E2) and climatic class (C2)
From IP00-IP56 enclosure with AN, AF, ANAF or AFWF cooling
Maintenance free
Environmental friendly ,>90% of material recyclable
Temperature control system
Built-in PT100 probes in 3 phase windings to detect the real-time temperature of windings and cycle display them in the digital screen.
Open circuit alarm and fault self-check alarm display and signal output.
3 stages automatically actions while the temperature reached to the set value, 1st stage the cooling fans start automatically, 2nd stage high temperature alarm,3rd stage over temperature trip.
Fans manual/auto control switch, timing start/stop, history data output.
4-20mA current output
RS485 Modbus communication protocol
Environment temperature measurement
Core temperature measurement
Scope of Supply
Product: Dry Type Transformer
Rated Power: Up to 20 MVA
Primary Voltage: Up to 35 KV
The transformer can be designed according to customer’s requirements
Technical Data Sheet
15 MVA dry type transformer specifications and data sheet
Delivered to | Montreal, Canada |
Year | 2016 |
Model | SGB-15MVA-24.94/4.16KV |
Type | Dry Type Transformer |
Standard | IEC60076 |
Rated Power | 15MVA |
Frequency | 60 HZ |
Phase | Three |
Cooling Type | ANAF |
Primary Voltage | 25 KV |
Secondary Voltage | 4.16 KV |
Winding Material | Copper |
Vector Group | Dyn11 |
Impedance | 5% |
Tap Changer | NLTC |
Tapping Range | ±2*2.5% |
Accessories | Standard Configuration |
15 MVA 24.94/4.16KV Transformer Manufacturing
Core
The core material is made of high-quality cold-rolled silicon steel sheet carefully laminated in full 45 diagonally.
Finished 15 MVA 24.94/4.16KV Transformer
Solution for harmonic influence:
1. Made of high-performance silicon steel sheet material and lower magnetic flux density design so as to withstand overvoltage and harmonic influence unsaturated.
2. Lower current density design and sufficient margin to make winding withstand additional temperature rise caused by harmonic.
3. Advanced insulation structure that can withstand a variety of over-load insulation impact.
4. Reaching up to maximum 27 phases for secondary winding in results a great reduction of the influence of the harmonic on the power grid and other equipment.
FAQ
1. How soon can you delivery the transformer?
It depends on the quantity and capacity of the transformer, normally within one month since the date drawing confirmed by buyer.
2. How long can you provide the quality warranty?
12 months since the date transformer operated.
3. What payment method do you accept?
T/T (wire transfer), L/C both accepted.
Thank you for your attention on Vouchivan ELECTRIC!
We offer Oil immersed transformers, Dry type transformers, Compact transformer substations, etc.Vouchivan Updated
-