Contact Us

315 KVA 3.3KV To 400V VPI Open Winding Dry Type Transformer

General introduction of   315 KVA 3.3KV To 400V VPI Open Winding Dry Type Transformer

VOUCHIVAN delivered two units of 315 KVA vacuum pressure impregnated (VPI) dry type transformer to South Africa in 2018.

  • Introduction
  • Contact Now

Product Introduction

The rated power of the transformer is 315 KVA. the primary voltage of the transformer is 3.3 KV and secondary voltage is 0.4 KV, the transformer coils are vacuum pressure impregnated in high temperature polyester vanish under vacuum and pressure, the coils can be made of copper or aluminum, the insulation is made of high grade nonflammable materials, the insulations class can be F(155℃), H(180℃)or C(220℃) class, suitable for different requirements, the finished coils are effectively protected against moisture, dirt, and most industrial contaminants, VPI transformers are suitable for use indoors or outdoors, any place require particular attention to the environments, such as costal and mining area, it can equipped with cooling fans and temperature controller to allow it have overload capacity. It’s maintenance free to save your valuable time and compact in size to save your limited space.


We ensure that each one of our delivered units has undergone rigorous full acceptance testing. We provide one-package service from consulting, quoting, manufacturing, installation, commissioning, training to after sale services, our products are now operating in more than 50 counties in the world. We aim to be your most reliable supplier as well as your best partner in business!


Advantages

Fire resistant /Self-extinguishing(F1)

Environmental class(E2) and climatic class (C2)

From IP00-IP56 enclosure with AN, AF, ANAF or AFWF cooling

Maintenance free

Environmental friendly ,>90% of material recyclable


Temperature control system

Built-in PT100 probes in 3 phase windings to detect the real-time temperature of windings and cycle display them in the digital screen.

Open circuit alarm and fault self-check alarm display and signal output.

3 stages automatically actions while the temperature reached to the set value, 1st stage the cooling fans start automatically, 2nd stage high temperature alarm,3rd stage over temperature trip.

Fans manual/auto control switch, timing start/stop, history data output.

4-20mA current output

RS485 Modbus communication protocol

Environment temperature measurement

Core temperature measurement


Scope of Supply

Product: resin cast dry type transformer

Voltage level: up to 35KV

Rating level: up to 20MVA

The transformer can be designed according to customer’s requirements


Technical Data Sheet

315 KVA Dry Type Transformer specifications and data sheet

Delivered to

Rwanda

Year

2016

Model

SG10 -315 KVA-3.3/0.4KV

Type

resin cast dry type transformer

Standard

IEC60076

Rated Power

315 KVA

Frequency

50 HZ

Phase

Three

Cooling Type

AN/AF

Primary Voltage

3.3 KV

Secondary Voltage

0.4 KV

Winding Material

Aluminum

Vector Group

Dyn11

Impedance

4%

Tap Changer

NLTC

Tapping Range

±2*2.5%

No Load Loss

0.88 KW

On Load Loss

3.47 KW

Accessories

Standard Configuration


General arrangement drawing

1



Finished 315 KVA 3.3/0.4KV Transformer




Why Insulation resistance of dry type transformer decreased:

1.Reason analysis. Pouring type dry transformer winding is mostly made of resin pouring, conductor material is sealed in it, so the decrease of insulation resistance is mostly caused by moisture condensation on the surface of winding, dust accumulation or part of insulation material being affected by moisture.

2.Processing method: Clean winding surface, surface moisture condensation with dry cloth wipe, natural air can be restored. It can be dried by heater and ventilated by fan. The neutral line (zero row) of the three-phase connection of dry-type transformer can be disconnected. The megohm meter is used to determine which phase the problem is in, and then the problem is carefully searched and processed.


FAQ

1. How soon can you delivery the transformer?

It depends on the quantity and capacity of the transformer, normally within one month since the date drawing confirmed by buyer.

2. How long can you provide the quality warranty?

12 months since the date transformer operated.

3. What payment method do you accept?

T/T (wire transfer), L/C both accepted.


Send us your detail requirements, we have professional service team to answer you ASAP!

Thank you for your attention on Vouchivan ELECTRIC!

We offer Oil immersed transformers, Dry type transformers, Compact transformer substations, etc.