250 KVA 0.69 KV Dry Type Transformer
General introduction of 250 KVA 0.69 KV Dry Type Transformer
The 250 kVA epoxy resin cast dry type transformer was delivered to Georgia in 2022. The rated power of the dry type transformer is 250 kVA, the primary voltage is 0.69 kV and secondary voltage is 0.4kV with delta star connection.
- Introduction
- Contact Now
Product Introduction
The 250 kVA epoxy resin cast dry type transformer was delivered to Georgia in 2022 for a national project. Transformers are used on the highway.
The rated power of the dry type transformer is 250 kVA with AN cooling, the primary voltage is 0.69 kV and secondary voltage is 0.4kV with delta star connection.
Cast resin technology provides excellent insulation and environmental protection, this together with the foil winding technology inside the resin offers the ultimate dry type transformer in terms of dielectric performance and short circuit withstand ability and ensures long term reliability for both distribution and special applications. cast resin transformers can be supplied with either aluminum or copper windings together with possibility of class F or class H insulation system, they can be designed to in-door or out-door installation with different enclosures.
We ensure that each one of our delivered units has undergone rigorous full acceptance testing. We provide one-package service from consulting, quoting, manufacturing, installation, commissioning, training to after sale services, our products are now operating in more than 50 counties in the world. We aim to be your most reliable supplier as well as your best partner in business!
Fire resistant /Self-extinguishing(F1)
Environmental class(E2) and climatic class (C2)
From IP00-IP56 enclosure with AN, AF, ANAF or AFWF cooling
Maintenance free
Environmental friendly ,>90% of material recyclable
Temperature control system
Built-in PT100 probes in 3 phase windings to detect the real-time temperature of windings and cycle display them in the digital screen.
Open circuit alarm and fault self-check alarm display and signal output.
3 stages automatically actions while the temperature reached to the set value, 1st stage the cooling fans start automatically, 2nd stage high temperature alarm,3rd stage over temperature trip.
Fans manual/auto control switch, timing start/stop, history data output.
4-20mA current output
RS485 Modbus communication protocol
Environment temperature measurement
Core temperature measurement
Scope of Supply
Product: resin cast dry type transformer
Voltage level: up to 35KV
Rating level: up to 20MVA
The transformer can be designed according to customer’s requirements
Technical Data Sheet
250 KVA Dry Type Transformer specifications and data sheet
Delivered to | Georgia |
Year | 2022 |
Model | SGB-250kVA-0.69/0.4kV |
Type | Resin cast dry type transformer |
Standard | IEC60076 |
Rated Power | 250 kVA |
Frequency | 50 HZ |
Phase | Three |
Cooling Type | AN |
Primary Voltage | 0.69 kV |
Secondary Voltage | 0.4 kV |
Winding Material | Aluminum |
Vector Group | Dyn11 |
Impedance | 4% |
Tap Changer | NLTC |
Tapping Range | N/A |
No Load Loss | 700 W |
On Load Loss | 2900 W |
Accessories | Wheels, Supporting Insulator on primary side, Plug type HV terminal, Lifting eyes, Earthing bolts, Temperature controller, PT100 probe, CT |
Remarks | N/A |
250kVA-0.69/0.4kV Transformer Drawing
250 kVA transformer diagram drawing and size.
Finished 250kVA-0.69/0.4kV Transformer
What is the difference between dry type transformer and oil?
Dry-type transformers use air as the cooling medium, while oil-filled transformers use oil instead of air. Some public places do not use oil-filled transformers because they are a big fire hazard and, instead, use dry-type transformers. This is because the liquid being used is flammable.
FAQ
1. How soon can you delivery the transformer?
It depends on the quantity and capacity of the transformer, normally within one month since the date drawing confirmed by buyer.
2. How long can you provide the quality warranty?
12 months since the date transformer operated.
3. What payment method do you accept?
T/T (wire transfer), L/C both accepted.
Thank you for your attention on Vouchivan ELECTRIC!
We offer Oil immersed transformers, Dry type transformers, Compact transformer substations, etc.Vouchivan Updated
-
Sep 20,2024
How should I choose between an oil-immersed transformer and a dry-type transformer? -
Sep 20,2024
What are the common outdoor substation technologies? -
Sep 20,2024
Causes and Considerations for Oil Leakage and Operating Temperature in Oil-Immersed Transformers